Synopsis of Work.
The first stage was the construction of the stud
framework on the workshop window wall. This was
followed by building the studwork on the two side
workshop walls. The final stage was the erection of the
9 joists spanning wall to wall across the workshop,
supporting the plasterboard ceiling and mezzanine
chipboard floor, with a sandwich fill of rockwool
insulation. Pressure treated soft-wood was used for all
the structural components.
Details
|
Wood for studwork delivered by Chiltern
Timber 8th June 2015.
Pressure treated wood for the stud walling and
partition wall frameworks, plus the 8 joists
supporting the new mezzanijne floor and
plasterboard ceiling. Not much room for
manoeuvre!
(Click picture for larger view)
|
|
Designing a stud framework to support the wall
sheathing
The design must take account of the maximum width
of the sheathing which, for the OSB boards used
in this project, have a width of 1,220mm. The
vertical studs to which the sheathing is screwed
should be spaced to accommodate the full width of
the boards with the joins located in the centres
of the studs. The exceptions are the first and
last boards in a given run where the vertical
board edges will locate at the edges of the
studs. The arrangement is shown in the diagram.
(Click picture for larger view)
|
|
Marking the positions for the vertical studwork
pieces. 17th June 2015
Marking the positions on the sole plate for the
70mm x 45mm vertical studwork, using steel tape,
pencil and set-square.
(Click picture for larger view)
|
|
Using a spirit level to ensure the studding is
vertical. 26th June 2015.
The spirit level is held against the upright
which is moved until the bubble is centred (as
shown in the inset). Holding the wooden upright
in its vertical position, The holes for the
fixings are then drilled into the masonry using
pre-drilled holes in the wood as guides.
(Click picture for larger view)
|
|
Diagram showing how studs are fixed to the
garage wall.
Sketch showing the hole sizes and depths for
fastening the 70mm x 45mm studs to the garage
walls.
The holes in the wooden stud were drilled first.
A cut stud was put in place on the brickwork, and
the position of the holes marked on the wood,
ensuring as far as possible, that the fixings
were in solid brick rather than in the encasing
mortar. The stud was then placed on the drill
table and a 16mm spade bit used to drill the 5mm
deep clearance hole for the hexagonal head of the
coach screw (also wide enough to accommodate the
end of the 10mm socket on the end of the ratchet
driver). The hexagonal heads of the coach screws
had to be recessed into the studs to allow for
the overlying OSB 3 sheathing. A 5mm wood drill
was then used to drill the hole for the M6 screw
body right through the stud. The stud was then
placed in position and the 5mm holes in the
wooden studs, used as guides for a 5mm masonry
drill to drill pilot holes in the garage wall
brickwork. The stud was then removed and the
pilot holes in the brickwork progressively
drilled, out with a series of masonry drills, to
a final diameter of 10mm and 55mm depth. The 10mm
plastic plugs were then pushed into the holes,
the stud placed in position and the 90mm long M6
coach bolts screwed home using the ratchet
spanner.
(Click picture for larger view)
|
|
Fastenings and Tools for the 70mm x 45mm
studwork.
Ratchet spanner with 10mm diameter socket (for
hexagonal headed coach screws); 10mm x 50mm long
plastic plugs; M6 hexagonal headed coach screws,
90mm long; M6 diameter steel washers; 5mm
diameter wood drill; 10mm diameter masonry drill;
16mm diameter spade bit for drilling a 5mm deep
hole in the wooden studs to take the hexagonal
heads plus washers on the coach screws.
(Click picture for larger view)
|
|
Jig used for accurate drilling of studs.
16th June 2015.
I could have used a power drill and unsupported
drilling for this but I preferred to use a drill
press for more accurate drilling. One end of the
stud rests on the circular drill press platform
whilst the other is supported using a combination
of a sash clamp in a Black & Decker
Workmate. The stud is levelled by means of the
sash clamp and once level, it can be clamped
(using a G clamp) in position on the drill press
table. The drill is started with a 16mm diameter
spade bit and brought down until the spade part
of the bit is just beginning to engage with the
wood. The drill is stopped but with the bit in
the same position (the spade just engaging with
the surface of the wood), the drill's depth gauge
is then set to 5mm, the drill re-started and the
hole drilled to that depth. Then, without
unclamping the wood, the spade bit is removed and
replaced with a 5mm twist drill bit. This is then
used to drill right through the stud. Because the
wood is still clamped, the 5mm hole aligns
perfectly with the centre of the 16mm hole, and
both holes are perpendicular to the stud.
(Click picture for larger view)
|
|
Drilling a 5mm pilot hole in the brick wall with
a masonry drill. 17th June 2015.
With the wooden stud wedged in position on the
wall, a 5mm masonry bit (used with a hammer
drill) can be put through each of the 5mm holes
in the studs to drill a series of pilot holes in
the brick wall of the garage. Make sure the
stud is securely wedged in position whilst
drilling to ensure that the masonry holes are in
exactly the correct position.
(Click picture for larger view)
|
|
Extending the 5mm pilot hole with a masonry
drill to the correct depth. 17th June
2015.
The wooden stud is then removed and the pilot
holes in the brickwork extended to the correct
depth ( > 50mm).
(Click picture for larger view)
|
|
Enlarging the 5mm pilot hole, with masonry
drills to 10mm diameter. 17th June
2015.
I find the easiest way to do this is to use a
series of drills, each drill 1 mm larger than the
previous. (6mm, 7mm, 8mm, 9mm & 10mm). This
may be tedious but it ensures accuracy and
minimises wear and tear on the masonry bits. The
final 10mm diameter bit is shown in the
photograph.
(Click picture for larger view)
|
|
Tapping the plastic plug into place into the
hole in the brickwork. 17th June
2015.
The 10mm diameter plastic plugs can be gently
tapped into the drilled holes in the brickwork.
(Click picture for larger view)
|
|
Stud in place with coach screw ready for driving
home. 17th June 2015.
The stud is placed back in position on the
brickwork and the coach screws driven through the
stud (ensuring that the ends are aligned to
engage with the underlying plastic plugs), ready
for driving home with the ratchet spanner.
(Click picture for larger view)
|
|
Using a ratchet spanner to drive home the
screws. 14th June 2015.
Using a ratchet spanner is much easier and more
effective than using a power or manual
screwdriver. Here the sole plate of the stud work
is being attached at the base of the window wall.
(Click picture for larger view)
|
|
Completed studwork for the end (Window) wall.
18th June 2015.
Photograph (top) of completed end wall studwork.
The original drawing for the studwork is shown
(bottom), to demonstrate a perfect match. This
part of the stud framework was completed on 18th
June 2015.
(Click picture for larger view)
|
Installing the Joists
Note added in response to Discussion of this project
on the Woodworkers Institute Forum (November
2016).
I'm most grateful to Peter Hyde for pointing out the
importance of using structurally graded and treated
timber of the correct size and length for the
load-bearing joists. The UK Building Regulations
provide a good tabular guide for this, which is
reproduced below.
Building Control Guidance Note:
Subject: DOMESTIC TIMBER FLOORS, Timber sizes and
construction details,
(Issued January 2010).
The following table gives details of allowable spans
and spacing between joists for the most common timber
sizes used in floor construction. All the figures are
based on normal domestic floor loadings where the floor
construction is typically 18-25mm floor boards/sheets
with up to 12.5mm thick plasterboard and skim
underneath. For any other situation these tables may
not be appropriate and you should refer to the TRADA
Document Span tables for solid timber members in
floors, ceilings and roofs for dwellings. When
choosing a joist spacing, check that your floorboards
(or sheets) are strong enough to span over the width
chosen. As a general rule - floorboards should be a
minimum 16mm thick for joist centres up to 500mm and
19mm minimum for centres up to 600mm.
FLOOR JOISTS SUITABLE FOR DOMESTIC FLOOR
LOADINGS
|
Width x thickness of joists
in mm.
|
Maximum allowed clear span in metres for a
joist spacing of:
|
400mm *
|
450mm *
|
600mm
|
97 x 47
|
1.93
|
1.82
|
1.47
|
120 x 47
|
2.52
|
2.42
|
2.05
|
145 x 47 *
|
3.04 *
|
2.92 *
|
2.59
|
170 x 47
|
3.55
|
3.42
|
3.00
|
195 x 47
|
4.07
|
3.91
|
3.41
|
220 x 47
|
4.58
|
4.39
|
3.82
|
145 x 75
|
3.54
|
3.10
|
3.10
|
170 x 75
|
4.14
|
3.99
|
3.63
|
195 x 75
|
4.72
|
4.52
|
4.13
|
220 x 75
|
5.15
|
5.01
|
4.67
|
Table assumes a minimum C16 structural grade timber
- not all timber is structurally graded - ensure you
purchase the right material!!
For this workshop project, the joists needed to clear
an unsupported span of 2.58m. Looking at the
above table, and checking the data against availability
of wood from local suppliers, I decided to opt for
pressure treated structural timber grade C16,
measuring 45mm (1¾") x 145mm (5¾"),
with spacing between the mid-points of the joists
measuring 405mm (1' 4"). This being nearest to
the dimensions in bold and marked thus
* in the above table.
I also followed the Building Regulations
recommendation: Where the joists span over 2.5m,
strutting is required to prevent joists twisting when
loaded. For spans of between 2.5 and 4.5m one row of
strutting is needed, at the mid span position.
The strutting was constructed exactly as recommended.
The timber for the joists and associated spacers, were
delivered in 3.0m lengths. Each of the 360mm long
spacing timbers were attached to the brick walls using
a single 90mm long, 6mm diameter hexagonal headed coach
screw in a 10mm diameter 50mm long plastic plug (as per
the studs).
The joists were screwed to the spacers using 65mm long,
6mm diameter hexagonal headed coach screws (two screws
at each end of the joist). Details follow.
|
Details of joist construction.
Drawing showing how the joists were constructed.
(Click picture for larger view)
|
|
Attaching a Spacer between the Joists.
6th July 2015.
This shows a spacer (between the joists) being
screwed to the brick wall. The clamp is used to
hold the spacer in exactly the right position as
the screw is driven home using the ratchet
spanner.
(Click picture for larger view)
|
|
Drilling attachment holes in a joist.
4th July 2015.
The joists were attached to the spacers using 4
(two at each end), 65mm long 6mm diameter
hexagonal headed coach screws. Here the holes for
two of the coach screws are being drilled, first
with a 16mm diameter spade bit (so that the
hexagonal head of the bolt can be recessed in the
joist), and then using a 5mm diameter drill to
make a hole right through the joist.
(Click picture for larger view)
|
|
Joist in position. 4th July 2015.
Joist in position, ready to be screwed to the
spacer. Note the wide 16mm diameter recess at the
top of the holes, so that the hexagonal bolt
heads can be hidden within the joist to allow for
the placing of the next spacer timber.
(Click picture for larger view)
|
|
Joist in position. 6th July 2015.
Joist in position, 65mm long 6mm diameter
hexagonal headed coach screws ready to be driven
home.
(Click picture for larger view)
|
|
Work in progress. 6th July 2015.
Work in progress installing the joists.
(Click picture for larger view)
|
Installing Strutting supports
UK Building Regulations state that where floor joists
span over 2.5m, strutting is required to prevent joists
twisting when loaded. For spans of between 2.5 and 4.5
m one row of strutting is needed, at the mid span
position. Solid strutting should be at least 38 mm
thick timber extending to at least three quarters the
joist depth. Here the 145mm x 45mm joists have timber
of the same width and thickness used as strutting.
|
Construction of anti-twisting strutting.
18th July 2015.
Photograph showing work in progress in fixing
anti-twisting struts to the joists. Each strut
measures 360mm x 145mm x 45mm. Two pilot holes
5mm in diameter, have been drilled through the
joist for fixing the end of the next strut.
(Click picture for larger view)
|
|
Fixing a New Strut in Place - 1. 18th July
2015.
In this photograph the new strut has been
positioned between the two adjacent joists and
temporarily jammed in place by applying pressure
(to the two containing joists), with a sash
clamp.
(Click picture for larger view)
|
|
Fixing a New Strut in Place - 2. 18th
July 2015.
With the strut jammed in place with the sash
clamp, the pilot holes are extended through the
joist and into the strut.
(Click picture for larger view)
|
|
Fixing a New Strut in Place - 3. 18th
July 2015.
With the strut jammed in place with the sash
clamp, the 6mm diameter, 80mm long woodscrews are
ready to be driven home. 18th July 2015.
(Click picture for larger view)
|
Installing Lighting Support Battens
Installing the strutting was also a good time to
install the battens which will support the 4 foot long
fluorescent light units. Details of how this was done
follows.
|
Fixing a new lighting support batten in place.
18th July 2015.
The same method as used for fixing the struts in
position, was used to fix the battens for
supporting the fluorescent lights. Here the two
6mm diameter fixing screws at one end of the
batten are ready to be driven home.
(Click picture for larger view)
|
|
Fluorescent Light Fitting. 18th July
2015.
Fluorescent light to be used in the workshop
showing the dimension needed between the mid
points of the two support battens.
(Click picture for larger view)
|
|
A Pair of Fitted Battens. 18th July
2015.
A pair of fitted fluorescent light battens
showing the correct dimension of 600mm between
their mid points.
(Click picture for larger view)
|
|
Completion of Joists. 18th July
2015.
Photograph of completed joists with strutting and
fluorescent light batten supports. A screenshot
from the original Sketchup drawing is
shown for comparison.
(Click picture for larger view)
|
|
Completion of Phase 2. 18th July
2015.
Photograph of completed studwork compared with a
screenshot from the original Sketchup
drawing.
(Click picture for larger view)
|
Phase 2 completed 18th July 2015.
Click HERE to return to the Home
Page.
© Tim & Trish Enterprises 2015-2017.